Answer Key: Self-Test D-1.8
1. Figure 2P-28
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Fixture drain | 4 | N/A | 3 in. | 
| B | Branch | 12 | N/A | 4 in. | 
| C | Branch | 16 | N/A | 4 in. | 
| D | Fixture drain — Sized as a wet vent — Acting as a relief vent | 1 | N/A | 2 in. | 
| E | Branch | 25 | N/A | 4 in. | 
| F | Circuit vent | 20 | 11 m | 1.5 in. | 
| G | Continuous vent — Acting as a relief vent | 5 | 3 m | 1.5 in. | 
| H | Branch vent | 25 | 11 m | 2 in. | 
2. Figure 2P-29
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Branch | 18 | N/A | 4 in. | 
| B | Branch | 42 | N/A | 4 in. | 
| C | Branch | 66 | N/A | 4 in. | 
| D | Fixture drain — Acting as a wet vent | 1 | N/A | 2 in. | 
| E | Branch | 73 | N/A | 4 in. | 
| F | Circuit vent | 66 | 16 m | 3 in. | 
| G | Additional circuit vent | N/A | N/A | 2 in. | 
| H | Branch vent | 66 | 16 m | 3 in. | 
| I | Relief vent | N/A | N/A | 2 in. | 
| J | Continuous vent | 7 | 4 m | 1.5 in. | 
| K | Branch vent | 73 | 16 m | 3 in. | 
3. Figure 2P-30
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Trap arm — Fixture drain | 4 | N/A | 3 in. | 
| B | Branch | 10 | N/A | 3 in. | 
| C | Branch | 20 | N/A | 4 in. | 
| D | Branch — Acting as a relief vent | 2 | N/A | 1.5 in. | 
| E | Branch | 26 | N/A | 4 in. | 
| F | Circuit vent | 24 | 13 m | 2 in. | 
| G | Dual and continuous vent — Acting as a relief vent | N/A | N/A | 1.5 in. | 
| H | Branch vent | 26 | 13 m | 2 in. | 
4. Figure 2P-31
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Trap arm — Fixture drain | 6 | N/A | 3 in. | 
| B | Branch | 18 | N/A | 4 in. | 
| C | Fixture drain — Sized as a wet vent — Acting as an additional circuit vent | 1 | N/A | 3 in. | 
| D | Branch | 30 | N/A | 4 in. | 
| E | Branch | 43 | N/A | 4 in. | 
| F | Branch | 67 | N/A | 4 in. | 
| G | Branch | 67 | N/A | 4 in. | 
| H | Circuit vent | 67 | 23 m | 3 in. | 
| I | Additional circuit vent | N/A | N/A | 2 in. | 
| J | Branch vent | 67 | 23 m | 3 in. | 
| K | Relief vent | N/A | N/A | 2 in. | 
| L | Branch vent | 67 | 23 m | 3 in. | 
5. Figure 2P-32
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Trap arm — Fixture drain | 6 | N/A | 3 in. | 
| B | Branch | 18 | N/A | 4 in. | 
| C | Branch | 42 | N/A | 4 in. | 
| D | Branch | 54 | N/A | 4 in. | 
| E | Fixture drain — Acting as a wet vent | 1 | N/A | 2 in. | 
| F | Branch | 62 | N/A | 4 in. | 
| G | Fixture drain — Acting as a relief vent | 1 | N/A | 1.5 in. | 
| H | Individual and continuous vent — Acting as a relief vent | N/A | N/A | 1.5 in. | 
| I | Circuit vent | 54 | 13 m | 2 in. | 
| J | Branch vent | 55 | 21 m | 3 in. | 
| K | Continuous vent | 7 | 7 m | 1.5 in. | 
| L | Branch vent | 62 | 21 m | 3 in. | 
6. Figure 2P-33
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Trap arm — Fixture drain | 4 | N/A | 3 in. | 
| B | Branch | 12 | N/A | 4 in. | 
| C | Branch | 28 | N/A | 4 in. | 
| D | Branch | 36 | N/A | 4 in. | 
| E | Branch | 44 | N/A | 4 in. | 
| F | Stack | 169 | N/A | 4 in. | 
| G | Circuit vent | 44 | 30 m | 3 in. | 
| H | Additional circuit vent | N/A | N/A | 2 in. | 
| I | Branch vent | 44 | 30 m | 3 in. | 
| J | Relief vent | N/A | N/A | 2 in. | 
| K | Branch vent | 44 | 30 m | 3 in. | 
7. Figure 2P-34
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Fixture drain | 4 | N/A | 3 in. | 
| B | Branch | 28 | N/A | 4 in. | 
| C | Branch | 40 | N/A | 4 in. | 
| D | Branch | 76 | N/A | 4 in. | 
| E | Branch | 88 | N/A | 4 in. | 
| F | Stack | 123 | N/A | 4 in. | 
| G | Stack | 35 | N/A | 4 in. | 
| H | Circuit vent | 88 | 31 m | 3 in. | 
| I | Additional circuit vent | N/A | N/A | 2 in. | 
| J | Branch vent | 88 | 31 m | 3 in. | 
| K | Additional circuit vent | N/A | N/A | 2 in. | 
| L | Relief vent | N/A | N/A | 2 in. | 
| M | Branch vent | 88 | 31 m | 3 in. | 
8. Figure 2P-35
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Branch | 8 | N/A | 3 in. | 
| B | Branch sized as a wet vent acting as a circuit vent | (2 – wv) 69 | N/A | 3 in. | 
| C | Branch | 20 | N/A | 4 in. | 
| D | Branch sized as a wet vent acting as an additional relief vent | 1 | N/A | 2 in. | 
| E | Trap arm fixture drain | 0.5 | N/A | 1.25 in. | 
| F | Branch | 45 | N/A | 4 in. | 
| G | Branch | 69 | N/A | 4 in. | 
| H | Branch acting as a relief vent | 8 | N/A | 2.5 in. | 
| I | Branch | 77 | N/A | 4 in. | 
| J | Dual and continuous vent acting as an additional circuit vent | N/A | N/A | 2 in. | 
| K | Circuit vent | 69 | 13 m | 3 in. | 
| L | Branch vent | 69 | 16 m | 3 in. | 
| M | Dual and continuous vent acting as a relief vent | N/A | N/A | 2 in. | 
| N | Branch vent | 77 | 16 m | 3 in. | 
9. Figure 2P-36
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Fixture drain | 4 | N/A | 3 in. | 
| B | Branch | 8 | N/A | 3 in. | 
| C | Branch | 12 | N/A | 4 in. | 
| D | Branch | 20 | N/A | 4 in. | 
| E | Branch | 39 | N/A | 4 in. | 
| F | Stack | 39 | N/A | 4 in. | 
| G | Stack | 19 | N/A | 3 in. | 
| H | Fixture drain | 3 | N/A | 3 in. | 
| I | Branch | 15 | N/A | 3 in. | 
| J | Stack | 4 | N/A | 2 in. | 
| K | Branch | 1 | N/A | 2 in. | 
| L | Branch | 3 | N/A | 2 in. | 
| M | Circuit vent | 20 | 33 m | 2 in. | 
| N | Relief vent | N/A | N/A | 1.5 in. | 
| O | Circuit vent | 15 | 26 mm | 2 in. | 
| P | Branch vent | 20 | 33 m | 2 in. | 
| Q | Branch vent | 35 | 33 m | 3 in. | 
| R | Circuit vent | 4 | 10 m | 1.5 in. | 
| S | Branch vent | 39 | 33 m | 3 in. | 
10. Figure 2P-37
| Letter | Name | Hydraulic Load (FU) | Length | Size | 
|---|---|---|---|---|
| A | Fixture drain | 4 | N/A | 3 in. | 
| B | Branch | 12 | N/A | 4 in. | 
| C | Trap arm — Fixture drain | 2 | N/A | 2 in. | 
| D | Fixture drain | 2 | N/A | 3 in. | 
| E | Branch | 18 | N/A | 4 in. | 
| F | Trap arm — Fixture drain | 1 | N/A | 1.25 in. | 
| G | Fixture drain | 1 | N/A | 2 in. | 
| H | Branch | 3 | N/A | 2 in. | 
| I | Branch | 21 | N/A | 4 in. | 
| J | Trap arm — Fixture drain | 1.5 | N/A | 1.5 in. | 
| K | Branch | 3 | N/A | 2 in. | 
| L | Branch | 25.5 | N/A | 4 in. | 
| M | Stack | 107 | N/A | 4 in. | 
| N | Sanitary building drain | 132.5 | N/A | 4 in. | 
| O | Relief vent | N/A | N/A | 1.25 in. | 
| P | Circuit vent | 4.5 | 30 m | 1.5v | 
| Q | Branch vent | 4.5 | 31 m | 2 in. | 
| R | Branch vent | 10.5 | 31 m | 2 in. | 
| S | Circuit vent | 6 | 22 m | 1.5 in. | 
| T | Combined relief vent | N/A | N/A | 1.5 in. | 
| U | Circuit vent | 12 | 21 m | 2 in. | 
| V | Branch bent | 22.5 | 31 m | 3 in. | 
| W | Branch vent | 25.5 | 31 m | 3 in. | 
| X | Branch vent | 3 | 24 m | 1.5 in. | 
| Y | Relief vent | N/A | N/A | 1.25 in. | 
| Z | Circuit vent | 3 | 24 m | 1.5 in. | 