Answer Key: Self-Test D-1.7

1. Figure 2P-18

Table 1 Answers
Letter Name Hydraulic Load (FU) Length Size
A Stack acting as a wet vent 7 N/A 3 in.
B Stack acting as a wet vent 7 N/A 3 in.
C Stack acting as a wet vent 7 N/A 3 in.
D Stack acting as a wet vent 7 N/A 3 in.
E Stack acting as a wet vent 7 N/A 3 in.
F Stack 8 N/A 3 in.
G Branch 8 N/A 3 in.
H Stack vent 8 4 m 3 in.

2. Figure 2P-19

Table 2 Answers
Letter Name Hydraulic Load (FU) Length Size
A Stack acting as a wet vent 3.5 N/A 3 in.
B Stack acting as a wet vent 3.5 N/A 3 in.
C Branch 9.5 N/A 3 in.
D Stack acting as a wet vent 1.5 N/A 2 in.
E Branch 7.5 N/A 3 in.
F Branch 17 N/A 3 in.
G Branch 17 N/A 3 in.
H Stack vent 7.5 4 m 1.5 in.
I Stack vent 9.5 4 m 1.5 in.

3. Figure 2P-20

Table 3 Answers
Letter Name Hydraulic Load (FU) Length Size
A Stack acting as a wet vent 1 N/A 1.5 in.
B Stack acting as a wet vent 1 N/A 1.5 in.
C Branch 2 N/A 1.5 in.
D Stack vent 2 3 m 1.25 in.

4. Figure 2P-21

Table 4 Answers
Letter Name Hydraulic Load (FU) Length Size
A Stack acting as a wet vent 6 N/A 3 in.
B Stack acting as a wet vent 6 N/A 3 in.
C Fixture drain 1.5 N/A 1.5 in.
D Branch – Wet vent 6 N/A 3 in.
E Branch – Wet vent 6 N/A 3 in.
F Branch 18 N/A 3 in.
G Individual and continuous vent N/A N/A 1.25 in.
H Stack vent 16.5 4 m 1.5 in.

5. Figure 2P-22

Table 5 Answers
Letter Name Hydraulic Load (FU) Length Size
A Stack acting as a wet vent 12 N/A 3 in.
B Stack acting as a wet vent 12 N/A 3 in.
C Stack acting as a wet vent 12 N/A 3 in.
D Stack acting as a wet vent 12 N/A 3 in.
E Stack 15 N/A 3 in.
F Stack vent 15 5 m 3 in.

6. Figure 2P-23

Table 6 Answers
Letter Name Hydraulic Load (FU) Length Size
A Stack acting as a wet vent 2.5 N/A 3 in.
B Stack acting as a wet vent 2.5 N/A 3 in.
C Stack 5.5 N/A 3 in.
D Branch 5.5 N/A 3 in.
E Stack vent 5.5 3 m 1.5 in.

7. Figure 2P-24

Table 7 Answers
Letter Name Hydraulic Load (FU) Length Size
A Branch 6.5 N/A 2.5 in.
B Trap arm — Fixture drain 3 N/A 2 in.
C Stack acting as a wet vent 3.5 N/A 2 in.
D Fixture drain 1.5 N/A 1.5 in.
E Stack acting as a wet vent 3.5 N/A 2 in.
F Individual and continuous vent N/A N/A 1.25 in.
G Stack vent 5 9 m 1.5 in.

8. Figure 2P-25

Table 8 Answers
Letter Name Hydraulic Load (FU) Length Size
A Branch 10.5 N/A 3 in.
B Trap arm — Fixture drain 6 N/A 3 in.
C Stack acting as a wet vent 4.5 N/A 3 in.
D Stack acting as a wet vent 4.5 N/A 3 in.
E Stack acting as a wet vent 4.5 N/A 3 in.
F Stack vent 10.5 6 m 1.5 in.

9. Figure 2P-26

Table 9 Answers
Letter Name Hydraulic Load (FU) Length Size
A Branch 17 N/A 3 in.
B Stack 17 N/A 3 in.
C Stack acting as a wet vent 7.5 N/A 3 in.
D Stack acting as a wet vent 7.5 N/A 3 in.
E Stack vent 17 10 m 1.5 in.

10. Figure 2P-27

Table 10 Answers
Letter Name Hydraulic Load (FU) Length Size
A Branch 4.67 N/A 3 in.
B Stack 4.67 N/A 3 in.
C Stack acting as a wet vent 4.17 N/A 3 in.
D Stack vent 4.67 6 m 1.5 in.